                                        Mircom MIX-101P Mini Priority Monitor Module
Description The module is supplied as a small plastic housing designed to fit into an electrical box. Six flying leads of 18AWG are used to connect the module. It also has a priority interupt facility to give fast response and can be fitted in an electrical box behind the pull station. Features Easy to install Low current draw Designed to meet a wide range of applications Addressable Eight position dip switch for address setting Each module can be addressed from 1 to 126 Fast response For use with the FX-350 Series Fire Alarm Control Panel Monitor modules can be wired as a Class A (Style D) or Class B (Style B) Technical Data Specifications Normal operating voltage 16-28 VDC Max wiring loop resistance 40 Ω Temperature range 32°F to 120°F (0°C to 49°C ) Humidity 0% to 95% (no condensing or icing) Monitored circuit current consumption Quiescent 600µA Alarm (LED on) 4.6mA End-of-line supervisory resistance 47KΩ, 0.5W Analog levels Open-circuit fault 4