Gamewell FCI AMM-4F Addressable Monitor Module
The Gamewell-FCI Velociti® Series, addressable monitor module (AMM-4F) features a single Style D, Class A initiating device circuit. Configured as a Style B, as well as Class B initiating circuit with end-of-line resistor. Also, this module provides an address for any device or group of devices connected to this circuit. Any alarm initiating devices with normally open (N.O.) dry contacts, such as heat detectors, linear heat detection devices, 4-wire projected beam smoke detectors, 4-wire smoke detectors, water flow switches, tamper switches, manual stations, etc. may be installed in this circuit. The AMM-4F module is design for installation in the signaling line circuit of any Gamewell-FCI analog addressable control panel. Furthermore, the initiating circuit of the AMM-4F has a maximum line resistance of 40 ohms, allowing the module to accommodate a number of initiating devices at a distance from the module. The initiating device circuit of the AMM-4F can support a maximum line resista