Mode: Direct Warrick Part Number: 26B1B0E Sensitivity: 10K Applications: Low-Water Cutoff Point Level Valve Control Alarms Pump Control Volt: 120V Style: 26 Open with 1/8" standoffs Features Power Outage: Non-Powered Contacts Time Delays Available LED Monitoring Snap-Thru Standoff Mounting Power Outage Feature Meets CSD1 Requirements U.L. "Limit Control"Designed for boiler low-water cutoff protection. A snap-through standoff mounting device is available for the Series 26. Optional Power Outage feature resets after nuisance outages. The optional reset button is used when the device has been deactivated because of low-water condition. Reset is functional only if water has returned to normal level. Built-in 3 second time delay is standard. Up to 90 seconds available for increasing and decreasing levels. Optional Dirty Electrode Detection Technical Documents: Series 26 LWCO Catalog Series 26 LWCO Instruction Bulletin * If the order is placed where the quantity or