RSDIN 6000 Amp 60 mV
DIN 43709 Compliant 60mV output ±0.5% tolerance (class 0.5) SPECIFICATIONS Type Rated Current (A) * Operating Current (A) Resistance (mn) RSDIN-6000-60 6000 4000 0.010 Rated Output 60mV Standard Custom outputs may be available on request Voltage Tolerance ±0.5% Standard Operating Temp. +30°C to +70°C Storage Temp. -55°C to 80°C Materials / Torque Specification Resistance Elements Manganin Terminal Blocks Brass Primary Hardware Torque 311Nm Zinc plated steel Bolts, Nuts, Washers Secondary Hardware Torque 4.3Nm Zinc plated steel Screws, Washers M5x8 Operating Current Derating: For continuous operation, it is recommended that shunts are not run at more than two thirds (2/3) the rated current under normal conditions per IEEE standards for DC instrument shunts. At ambient tempera- tures above 40°C, the current must be further derated to prevent damage.