HiC2873, Solenoid Driver
Solenoid Driver, HiC2873 1-channel isolated barrier 24 V DC supply (bus or loop powered) Output 40 mA at 12 V DC, 55 mA current limit Contact or logic control input Entity parameter Io/Isc = 110 mA Line fault detection (LFD) Test pulse immunity Up to SIL 2 acc. to IEC 61508 (bus powered) Up to SIL 3 acc. to IEC 61508 (loop powered) This isolated barrier is used for intrinsic safety applications. The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area. It is controlled with a loop powered control signal, switch contact, transistor, or logic signal. At full load, 12 V at 40 mA (with 55 mA current limit) is available for the hazardous area application. Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. This device mounts on a HiC termination board.