HiD2872, Solenoid Driver

HiD2872, Solenoid Driver

$431.87
{{option.name}}: {{selected_options[option.position]}}
{{value_obj.value}}

Solenoid Driver, HiD2872 2-channel isolated barrier 24 V DC supply (bus or loop powered) Output 40 mA at 12 V DC, 55 mA current limit Contact or logic control input Entity parameter Io/IscĀ = 110 mA Line fault detection (LFD) Up to SIL 2 acc. to IEC/EN 61508 (bus powered) Up to SIL 3 acc. to IEC/EN 61508 (loop powered) This isolated barrier is used for intrinsic safety applications. It supplies power to solenoids, LEDs, and audible alarms, located in a hazardous area. It is controlled with a loop-powered control signal, switch contact, transistor, or logic signal. At full load, 12 V at 40 mA (with 55 mA current limit) is available for the hazardous area application. An alternative low current output is available for driving a single LED without installing an external current limiting resistor. Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. This device mounts on a HiD Termination Board.

Show More Show Less